Red-lion CTL Manuale Utente Pagina 1

Navigare online o scaricare Manuale Utente per Accessori per computer Red-lion CTL. Red Lion CTL User Manual Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 2
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA
JUMPER SELECTABLE RANGES
OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT
SPLIT-CORE AND FIXED-CORE CASES
GENERAL DESCRIPTION
CTL Series transducers combine a current transformer and a signal conditioner
into a single package. This provides higher accuracy, lower wiring costs, easier
installation and saves valuable panel space.
The CTL Series transducers have jumper selected current input ranges and
industry standard 0-10 VDC or 4-20 mA outputs. The CTL Series is designed for
application on “linear” or sinusoidal AC loads. Available in a split-core or solid-
core case. Select the CTL Series for constant speed loads or On/Off loads.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons or
equipment in the event of a fault to the unit.
SPECIFICATIONS
7. INPUT RANGES: (Jumper Selectable)
8. ISOLATION VOLTAGE: 3 kV
9. CASE: UL 94V-0 Flammability rated thermoplastic
10. ENVIRONMENTAL: -4 to 122 °F (-20 to 50 °C)
0-95% RH, non-condensing
11. TORQUE RATINGS: 7 in-lbs on Fixed-core models; 9 in-lbs on Split-core
models.
12. LISTING: UL 508 Industrial Control Equipment, CSA C22.2 No. 14-M95,
and CE Certified.
MODEL CTL - AVERAGE RESPONDING AC CURRENT TRANSDUCERS
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Bulletin No. CTL-C
Drawing No. LP0652
Released 03/14
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
C
US LISTED
U
L
R
IND. CONT.
EQ.
5T44
PART
NUMBER
RANGE
MAXIMUM
6 secContinuous 1 sec
CTL050
_ _
CTL005
_ _
2 A 125 A80 A 250 A
5 A 125 A100 A 250 A
50 A
20 A
10 A
215 A
150 A
125 A
175 A
110 A
80 A
400 A
300 A
250 A
CTL200
_ _
100 A 300 A200 A 600 A
150 A 450 A300 A 800 A
200 A 500 A400 A 1000 A
0.85
(21.6)
0.85
(21.6)
3.53
(89.7)
2.40
(61)
3.04
(77.2)
Ø 0.19
(4.8)
2.25
(57.2)
1.19
(30.2)
DIMENSIONS In inches (mm)
3.50
(88.9)
3.03
(77.0)
0.93
(23.6)
Ø 0.19
(4.8)
2.40
(61.0)
2.18
(55.4)
Ø 0.74
(19)
DIMENSIONS In inches (mm)
0-10 VDC 4-20 mA
1. OUTPUT SIGNAL: 0-10 VDC 4-20 mA
2. OUTPUT LIMIT: 15 VDC 40 mA
3. FREQUENCY RANGE: 50-60 Hz 20-100 Hz
4. RESPONSE TIME: 100 msec 300 msec
6. POWER SUPPLY:
5. ACCURACY:
Self-powered
1.0% FS 0.5% FS
SPLIT-CORE
FIXED-CORE
24 VDC Nominal, 40 VDC max.
Vedere la pagina 0
1 2

Sommario

Pagina 1 - US LISTED

 AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA JUMPER SELECTABLE RANGES OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT SPLIT-CORE AND FIXED-C

Pagina 2 - TROUBLE SHOOTING

INSTALLATIONRun wire to be monitored through opening in the sensor. The CTL Series transducers work in the same environment as motors, contactors, hea

Commenti su questo manuale

Nessun commento